When ordered as an option, continuous run xtures use quick-connectors and keyhole fasteners to properly wire & align the joining xtures.
5 6
7
Shift xtures until keyhole studs lock-in place and xtures
are horizontally aligned
Install two #8-32 screws with nuts (provided) to fasten the
end plates of the joined xtures together
Continue to add xtures as needed to complete the
continuous run.
Note: If there are unused quick-connectors at the end
of a run, cut off the connectors and cap the ends with
wire connectors to terminate the wires. Replace open
end plate with a solid end plate.
Note: The current though the continuous xture run cannot
exceed 20A. See maximum xture run length listed below.
Output
Voltage
Total Run Length (ft.)
T H V
120V 288 192 120
277V 664 440 284
347V 677 495 342
480V 936 685 474
3 4
Push the quick-connect assembly and excess wiring
into the open end of one xture end plate so only a
small length of wire remains between joining xtures.
Align keyhole slots with corresponding keyhole studs and
push xtures together.
Continuous Run Installation
1 2
Completely hang the rst xture in the run. One end
should be closed while the other end has quick-connect
wiring. Using two people, hang the next xture in the run,
making sure to properly align quick-connectors.
Make all wiring connections between xtures using the
provided quick-connectors.
Closed end
First xture in run
Open end