AREA LIGHTING
Guide Form Specifications 2011
g
GE
Lighting Solutions
GUIDE FORM SPECIFICATIONS
GENERAL DESCRIPTION
The totally enclosed and weather-resistant luminaire designat-
ed _______ (identify) shall be a GE WALLIGHTER 400 luminaire,
ordering number _______ (specify W4L, plus ordering number
logic from catalog), or approved equal, to operate one _______
(specify [150(55V), 200, 250 or 400] watt high pressure sodium
[HPS], [175, 250 or 400] watt metal halide, or [175 or 250] watt
mercury) lamp from a nominal _______ (specify 120, 208, 220,
240, 277, 347 or 480 volt, 60 Hz or 220 or 240 volt, 50 Hz) pow-
er source. The luminaire shall include a completely prewired
integral ballast and an optical assembly that shall provide an
IES Distribution Type _______ (specify according to photometric
selection table in catalog). The luminaire shall be UL/cUL Listed
SUITABLE FOR WET LOCATIONS and UL Listed to meet Canadian
National Standards and Codes . Standard construction is IP55.
Ballast, housing, optical and luminaire assembly shall all be
from the same manufacturer.
OPTICAL ASSEMBLY
WALLIGHTER 400 LUMINAIRE
The sealed optical assembly shall have an activated-charcoal
filter enabling it to breathe as the unit heats and cools. The hy-
droformed aluminum reflector shall have a chemically bonded
lightweight non-breakable ALGLAS
®
finish on all surfaces for
precise light control in combination with the impact-resistant
tempered prismatic glass refractor. The optical assembly shall
contain a mogul base E39 socket with superior lamp gripping.
The socket shall have added insulation, giving it the ability to
handle the higher pulse ratings of newer HID systems. The
reflector and socket shall be easily removed with only a screw
driver for a tool.
* REFER TO PRODUCT PAGE FOR BALLAST SELECTIONS. FOR
MORE DEFINITIVE INFORMATION, REFER TO BALLAST SPECIFICA-
TIONS IN TECHNICAL DATA SECTION.
BALLAST OPERATION
The luminaire shall have a standard _______ (specify) bal-
last*. The plug-in type ignitor (for HPS only) and ballast shall
be prewired to the lamp socket requiring connection of power
supply leads only. The ballast shall be in full compliance with
lamp-ballast specifications available to the fixture manufac-
turer from the lamp manufacturers at the time of fixture manu-
facture.
The ballast shall reliably start and operate the lamp in ambient
temperatures down to -2F for mercury and metal halide and
-40°F for HPS.
MECHANICAL CONSTRUCTION
The luminaire shall include a die-cast aluminum housing with
ballast, prewired terminal board, sealed and filtered optical
assembly and a die-cast aluminum side-hinged door with glass
refractor sealed to it. Die-cast aluminum surfaces shall have an
electrocoat dark bronze paint finish. Mounting shall be by three
bolts through back holes provided for mounting on vertical or
horizontal surfaces. There shall be ¾-inch (19mm) NPT conduit
entrances (and provisions for an optional prewired photoelec-
tric receptacle.
Seitenansicht 0
1 2

Inhaltsverzeichnis

Seite 1 - WALLIGHTER 400 LUMINAIRE

AREA LIGHTINGGuide Form Specifications – 2011gGE Lighting SolutionsGUIDE FORM SPECIFICATIONSGENERAL DESCRIPTIONThe totally enclosed and weather-resis

Seite 2 - 1 6 9 4 3 5 3 3- - -- 8 8 8

gGE Lighting Solutions is a subsidiary of the General Electric Company. Evolve and other trademarks belong to GE Lighting Solutions. The GE brand and

Kommentare zu diesen Handbüchern

Keine Kommentare