The Luminaire wattage is preset at the factory. Please contact the
factory for instructions and a retrofit kit if a different wattage is
required.
Black Color = Primary Phase
White Color = Neutral or Secondary
Phase
Green Color = Fixture - Earth Ground
Violet Color = (+) 0-10VDC Dimming
Gray Color = (-) 0VDC Dimming
All
Nuvation
Models
Dimming
Nuvation
The NuVation ballast is rated for use with a supply voltage
between 208V and 277V with +/- 10% line voltage tolerance, 50/
60 Hz, and will automatically sense voltage within the specified
range.
The wire colors for the input lines in the wiring box are:
DC Control Voltage 0V +5V +10V
Output Level 50% 75% 100%
CAUTION
Risk of Electrical Damage
• DO NOT MISMATCH wattage setting
and Metal Halide HID Lamp wattage.
• Verify that the circuit wiring and
circuit breakers are rated for the total
circuit load.
DIMMING FEATURE / INSTRUCTIONS
The NuVation
™
meets the lamp manufacturers requirements of
starting/operating the lamp at high wattage for at least 15
minutes before any dimming control can happen.
For continuous operation (24 hr/day) the NuVation will
automatically go into a full power mode once a day for at least 15
minutes as required by lamp specifications.
WIRING NOTES: Polarity of the dimming control leads
(VIOLET + and GRAY -) must be maintained.
DIMMING CONTROL
Dimming control is accomplished by connection to the
VIOLET + AND GRAY –
Wires in the wiring box (Figure 2). See Diagram A for wiring
schematic.
POLARITY MUST BE PROPERLY APPLIED
(VIOLET + To control +) AND (GRAY – To control -)
Shorting (example with a switch) the violet and gray wires will
cause the NuVation to operate at low wattage, removing the short
will cause the lamp to operate at full wattage.
External control systems can be used to operate the bi-level
function.
Diagram A
A zero (0) to ten (10) volt DC power supply can control the bi-level
operation.
This can be either to continuously adjustment lamp wattage 50%
to 100 %.
Or one step 50% to 100%.
POLARITY MUST BE PROPERLY APPLIED
(VIOLET + To control +) AND (GRAY – To control -)
A resistor or potentiometer (pot) can also be used to continuously
adjust lamp wattage by connecting to the VIOLET + and GRAY –
wires. The resistor or potentiometer should be in the 0 – 50K ohm
range. The voltage output from the VIOLET + and GRAY – wires will
be in the 0-10 volt range and current will be less than one (1)
milliamp.
Added Features of the GELS NUVATION ™
• Automatic lamp shut off if the lamp fails to start within 90
minutes
• After a power shut off the NUVATION must be switched off and
then back on (cycle time 1 to 2 seconds).
Automatic lamp shut off for end of life high voltage lamps
FINAL ASSEMBLY
OPTICAL ASSEMBLY/MOUNTING
UGE, VBE, UWE, UTE, OBE, UME, MBE
1. Secure the reflector to the bottom of the ballast housing as
shown in Figure 6. Installation is aided by keyhole slots in
reflector.
1a. On VBE and MBE units with Safety Chains, orient the reflector
so that the Ballast Housing and Reflector Safety Chain
Attachment Holes are on the same side.
1b. On VBE units push the Reflector Mounting Bracket thru the
reflector opening and slide it over the Socket Brackets all the
way. On 400 watt Metal Halide units the top (first) hole of the
Mounting Bracket will snap over the Socket Bracket screws.
On all others, the bottom (second) hole will snap over the
bracket screws. See Figure 7. For additional assembly
instructions, refer to the instruction sheet that came in the
small box with the metal reflector and -mounting bracket.
Keyhole
Slots
Reflector
Figure 6 Figure 7 Figure 8
Locking
Tabs
Locking
Tabs
Socket
Socket
Quartz
Socket
Kommentare zu diesen Handbüchern