WIRING
Make all electrical connections in accordance with the National Electrical Code and any applicable
local code requirements.
Verify that supply voltage is correct by comparing it to nameplate.
If unit is designated as multivolt or multiwatt, follow specific instruction.
Installer needs to connect supply conductors to primary leads and fixture ground wire. These wires
are located on the small wiring harness that contains the 9-pin plug. After these wires are connected, the
9-pin plug wired in the fixture needs to be mated with the 9-pin plug wired to the supply conductors
(assuming that they are not already connected). Removal of the 9-pin plug does not hinder the electrical
performance of the luminaire.
NOTE: Attach ground conductor to the green ground wire supplied with the fixture.
FINAL ASSEMBLY
OPTICAL ASSEMBLY/MOUNTING—
1. Secure reflector to bottom of ballast housing using two of the four screws provided. Installation is
aided by key hole slots in reflector. On VBC units with safety chains, orient the reflector so that the
ballast and reflector holes are on the same side.
2. Using the remaing two screws attach the pan. Installation is aided by key hole slots in bracket.
3. Refer to LAMP INSTALLATION and snap lamp into socket.
4. (For enclosed units only) Close door and secure properly in place by latching first latch opposite hinge,
followed by other latches.
LAMP INSTALLATION/REPLACEMENT
SAFETY CHAINS
CAUTION: When used, safety chains must be carefully installed as outlined below.
Safety chains may be attached to luminaire when user feels safety chains should be used. Safety
chains should be attached in a manner to give minimum slack. In no case should a ballast or optical safety
chain be installed in a manner which permits luminaire to fall more than six (6) inches before it is caught
by chain. To install ballast safety chain, insert “S’’ hook through hole in housing and crimp shut. Safety
chains and attachment accessories are available from factory as an optional accessory for both ballast
and optical assemblies.
To install optical safety chain, insert “S” hook through a link in ballast safety chain and crimp shut. Use
snap hook to attach to clip or hole on optical. See figure 4.
CAUTION
Risk of burn
• Allow lamp/fixture to cool before handling
Figure 4
The light output of a luminaire is dependent on the age of the lamp. In applications where light level
is critical it may be desirable to replace lamps before they burn out. Lamp manufacturer can provide
data showing how lamp light output decreases with use.
Use only lamps specified on socket ASM lamp label. Observe lamp manufacturer’s recommendations
and restrictions on lamp operation, particularly ballast type, burning position, etc.
Figure 3
MAINTENANCE
It will occasionally be necessary to clean outside of refractor to maintain light level. Frequency of
cleaning will depend on ambient dirt level and minimum light level which is acceptable to user. Lens door
(if enclosed) should be washed in a solution of warm water and any mild,
non-abrasive household detergent, rinsed with clean water and wiped dry. Should optical assembly
become dirty on inside, wipe reflector and clean lens door in above manner, and replace any damaged
gasket.