GE MN-ValVue-v2-8-IOM Wartungshandbuch Seite 553

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 660
  • Inhaltsverzeichnis
  • FEHLERBEHEBUNG
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 552
553
Transmitter Diagnostics Tab
Transmitter Diagnostics Tab
See “Monitor Tab” on page 527 for nameplate data configuration.
Figure 10 Transmitter Diagnostics Tab
Smart Filtering Coefficients
These three parameters suppress the noise, the waves in the displacer chamber or the
mechanical vibration to smooth the current output:
W Integ: Integration window expressed in seconds. The value must be between 0.1
and 32.0 seconds.
DZ Integ: Dead Zone Integration is expressed in percent of zero/span calibration. The
value must be between 0.01% and 10.0 %.
W Val: Validation window is expressed in seconds. The scale must be between 0.1
and 32.0 seconds.
Seitenansicht 552
1 2 ... 548 549 550 551 552 553 554 555 556 557 558 ... 659 660

Kommentare zu diesen Handbüchern

Keine Kommentare