EPM 3000P THREE-PHASE DIGITAL VOLT/AMPS MONITOR EPM 3000P –F THREE-PHASE VOLTS/AMPS/FREQUENCY MONITOR Instruction Manual
Chapter 2 Electrical Installation +-POWER76543218910111213PORTL1LLINEABCLOAD3-PHASE, 3-WIRE DELTABACK VIEWWITH DIRECT VOLTAGE AND CTsCONTROL I. Thr
Chapter 2 Electrical Installation +-POWER7654321891011 12 13PORTL1LLINEABCLOAD3-PHASE, 3-WIRE OPEN DELTABACK VIEWWITH 3 CTs AND 2 PTs III. Open Delt
Chapter 2 Electrical Installation 765432189101112 13LINENABCLOAD3-PHASE, 4-WIRE WYEL1L2POWER+-PORTBACK VIEWWITH CTs AND PTs V. Three Phase System W
Chapter 2 Electrical Installation 7 6 5 4 3 2 1 8 9 10 11 12 13 LINE A B LOAD DUAL-PHASE WITH CTs AND Direct Voltage L1 L2 POWER + - PORT BACK VI
Chapter 2 Electrical Installation Figure 2.1 - Relay Connection Close-up of the relays on the rear panel. The relays shown are in the NOT energize
CHAPTER 3 COMMUNICATION INSTALLATION 3.1 RS-232C All EPM3000P and EPM300P-F instruments can be equipped with: the EIA RS-232C or the EIA RS-485. RS
Chapter 3 Communication Installation RS-485 is used to parallel multiple instruments on the same link. Its operating capability is up to 4000 feet.
Chapter 3 Communication Installation RS-485 Hookup Diagram (2 wire) Half Duplex: Detail ViewGR+T+R-T- GR+T+R-T-RS-485CommunicationsPortModel#SF48
CHAPTER 4 EPM3000P OVERVIEW The EPM3000P and EPM3000P-F measure 10 electrical parameters. Values for each parameter are accessed through the keypad o
Chapter 4 EPM3000P Overview 4.2 RESETTING VALUES FROM OPERATING MODE Use the reset function if a new value is desired. It is available in two diffe
All Rights Reserved. Printed in the United States of America. NORTH AMERICA GE Industrial Systems, 41 Woodford Avenue, Pla
Chapter 4 EPM3000P Overview MAXAC VOLTSA B C NAC AMPSMAX/MINLIMITSVOLTSPRINTPROGPHASENEXTAMPSB C AI I IA B CN N NI I IA B CLM2LM1
Chapter 4 EPM3000P Overview MAXAC VOLTSA B C NAC AMPSMAX/MINLIMITSVOLTSPRINTPROGPHASENEXTAMPSB C AI I IA B CN N NI I IA B CLM2LM1
Chapter 4 EPM3000P Overview ÖTo PRINT THE OPERATING DATA, follow these steps: MAXAC VOLTSA B C NAC AMPSMAX/MINLIMITSVOLTSPRINTPROGPHASENEXTAMPSB
Chapter 4 EPM3000P Overview 4.7 LED TEST FROM OPERATING MODE The EPM3000P is equipped with an LED test to check if the LEDs and annunciators are fu
PROGRAMMING YOUR EPM3000P CHAPTER 5 GENERAL PROCEDURE OVERVIEW 5.1 HOW TO USE THIS PORTION OF THE MANUAL This manual contains programming for basic
Chapter 5 General Procedure Overview 5.3 PROGRAMMING MODE ENTRY USED FOR PASSWORD ENTRY MAX/MIN LIMITS VOLTS AMPS PRINT PROG PHASE NEXT USED
CHAPTER 6 ENTERING THE PROGRAMMING MODE 6.1 CHECKSUM ERROR - PROTECTIVE MECHANISM If the control power is interrupted while in Programming Mode or
CHAPTER 7 PROGRAMMING GROUP 0: GLOBAL METER SETUP The Global Meter Setup includes Functions 0 through 5 that control configuration and basic operatio
Chapter 7 Global Meter Setup 7.2 GROUP 0, FUNCTION 1 - THE METER ADDRESS METER ADDRESS: Identifies the meter when communicating with a computer sys
Chapter 7 Global Meter Setup MAXAC VOLTSA B C NAC AMPSMAX/MINLIMITSVOLTSPRINTPROGPHASENEXT0.AMPSB C AI I IA B CN N NI I IA B CLM
Customer Service and Support Customer service and support is available 24 hours a day, 7 days a week. Please have the model, serial number and a deta
Chapter 7 Global Meter Setup ÖPress PRINT/PROG to scroll from PACK to PACK. MAXAC VOLTSA B C NAC AMPSMAX/MINLIMITSVOLTSPRINTPROGPHASENEXT03.PAMP
Chapter 7 Global Meter Setup 7.5 GROUP 0, FUNCTION 3 - PROGRAMMING PROCEDURE ÖTo change the SYSTEM CONFIGURATION SWITCH settings, follow these step
Chapter 7 Global Meter Setup EXAMPLE 1: Relay 1 will be “SET” once the reading exceeds 5.00 amps. Relay 1 will be “RESET” once the reading falls be
Chapter 7 Global Meter Setup ÖTo change the TIME DELAY FOR RELAY 1 OR RELAY 2, follow these steps: PRESS MAX/MIN/LIMITS, AT ANY TIME, TO CANCEL BEF
CHAPTER 8 PROGRAMMING GROUP 1 8.1 SCALE SELECTIONS AND FULL SCALE SETTINGS Programming GROUP 1 functions provide a selection of Full Scale Settings
Chapter 8 Programming GROUP 1 MAXAC VOLTSA B C NAC AMPSMAX/MINLIMITSVOLTSPRINTPROGPHASENEXTI0AMPSB C AI I IA B CN N NI I IA B CLM
CHAPTER 9 PROGRAMMING GROUP 2: METER CALIBRATION 9.1 STANDARD CALIBRATION WARNING - READ THIS SECTION CAREFULLY BEFORE PROCEEDING ⌦ Calibration d
Chapter 9 Programming GROUP 2: Meter Calibration 9.2 GROUP 2, FUNCTIONS 0-8: HIGH END CALIBRATION OF VOLTAGE CHANNELS, HIGH & LOW END CALIBRAT
Chapter 9 Programming GROUP 2: Meter Calibration FOR FUNCTIONS 6 THROUGH 8, FOLLOW THESE STEPS: NOTE: PRESS MAX/MIN/LIMITS, AT ANY TIME, TO CAN
CHAPTER 10 PROGRAMMING GROUP 4: SET LIMITS & RELAYS GROUP 4 contains LM1 and LM2 set limit values for the voltage and amperage scale allowing the
TABLE OF CONTENTS I N S T A L L A T I O N & O P E R A T I O N CHAPTER 1 MECHANICAL INSTALLATION 1 Installation of the EPM3000P with K-
Chapter 10 Set Limits & Relays GROUP 4, FUNCTIONS 0 - 3: LM1/LM2 SET LIMITS MAXAC VOLTSA B C NAC AMPSMAX/MINLIMITSVOLTSPRINTPROGPHASENEXT
Chapter 10 Set Limits and Relays ÖTo program LIMITS OR RELAYS, follow these steps: NOTE: PRESS MAX/MIN/LIMITS, AT ANY TIME, BEFORE STORING THE LAS
Chapter 10 Set Limits & Relays MAXAC VOLTSA B C NAC AMPSMAX/MINLIMITSVOLTSPRINTPROGPHASENEXT40AMPSB C AI I IA B CN N NI I IA
CHAPTER 11 PROGRAMMING GROUP 7: PHASE REVERSAL & PHASE IMBALANCE SET LIMITS/RELAYS 11.1 VOLTAGE PHASE REVERSAL AND PHASE IMBALANCE The set limit
Chapter 11 Phase Reversal & Phase Imbalance Set Limits/Relays 11.3 GROUP 7, FUNCTION 0: VOLTAGE PHASE REVERSAL DETECTION ÖTo change the PHASE R
Chapter 11 Phase Reversal & Phase Imbalance Set Limits/Relays 11.4 GROUP 7, FUNCTION 1: PERCENTAGE VOLTAGE PHASE IMBALANCE ÖTo change PERCENTA
CHAPTER 12 EXITING THE PROGRAMMING MODE NOTE: STEPS TO EXIT THE PROGRAMMING MODE VARIES AS THE PROGRAMMING STAGE VARIES. Exiting the Programming Mo
TABLE OF CONTENTS P R O G R A M M I N G CHAPTER 5 GENERAL PROCEDURE OVERVIEW 19 Section 5.1 How to Use This Portion of the Manual 19 5.2 Switch P
INSTALLATION & OPERATION CHAPTER 1 MECHANICAL INSTALLATION The following diagrams display the various possible EPM3000P and EPM3000P-F mechanic
Chapter 1 Mechanical Installation FIRST PUT (16) PIN CONNECTOR TOGETHER.(2) 8-32 SCREWS WILLSIDE VIEW0.80(4) 8-32 SCREWSLINE UP WITH 2 PEMSON THE BA
CHAPTER 2 ELECTRICAL INSTALLATION 2.1 CONNECTING THE CURRENT CIRCUIT The cable used for the current should be installed at 600V AC minimum. The cabl
Chapter 2 Electrical Installation 2.5 ELECTRICAL CONNECTION INSTALLATION Choose the diagram that best suits your application and maintain the polari